Chapter 12.14 CONTROL OF BACKFLOW AND CROSS-CONNECTIONS
Section 12.14.070 Booster pumps.
1. No person shall install or maintain a water service connection to any premises
where a
booster pump has been installed on the service line to or within such premises, unless such
booster pump is equipped with a low pressure cut-off designed to shut-off the booster pump
when the pressure in the service line on the suction side of the pump drops to twenty (20) pounds
per square inch gauge or less.
2. It shall be the duty of the water customer to maintain the low pressure cut-off
device in
proper working order. (Ord. 2006-0369;93/U-954)
(2006-0369, Amended, 05/23/2006, Prior Text)