Chapter 20.08 ELECTRICAL CODE
Section 20.08.110 Rewiring, additions to, and conversions of residential buildings.
The following are the minimum requirements for rewiring of, any additions to, and conversions
of residential buildings.
1. General.
a. Where rewiring and conversions are
being constructed, and wiring methods not approved
by these installation standards exist, or when it is necessary to increase, change or move the
service other than service replacement as required in paragraph b. of this subsection, all new
wiring or rewiring to be installed and all hazardous wiring to be replaced shall comply with the
standards in this chapter.
b. Where additional wiring or structural
additions are being made to existing structures, all
new wiring installed, including the service entrance or service panel, shall meet the National
Electrical Code as adopted by the city.
2. Conversions.
a. The wiring in any building being
converted from one business or commercial occupancy
to another in combination with a residence will comply with the wiring requirements of a
business or commercial building.
b. All new wiring or rewiring done in
the conversion of a building, as well as the
replacement of existing wiring which presents a hazard, shall be installed according to this
chapter.
EXCEPTION: The residential portion of the existing building
may be wired as a residence;
provided, that approved fire separation requirements as set forth in the city building code are met
and maintained between the commercial and residential portions of the building.
3. Garages and Accessory Buildings.
a. Attached garages shall have at least
one GFCI protected grounded duplex wall receptacle
and one ceiling or wall light controlled by a wall switch.
b. Detached garages or accessory buildings
which are wired shall have at least one GFCI
protected grounded duplex wall receptacle and one ceiling or wall light controlled by a
wall
switch.
c. All 120 volt garage receptacles shall
be GFCI protected.
EXCEPTION 1: Receptacles which are not readily accessible.
EXCEPTION 2: Dedicated outlets which shall be identified
as such.
Excepted outlets shall be in addition to the required GFCI outlet
required in (a) and (b) above.
4. Receptacles.
a. Outdoor receptacles shall be grounded
and GFCI protected as required by the National
Electrical Code.
b. Laundry receptacles shall be grounded
and be on a separate twenty ampere circuit.
c. Receptacles and wiring in the kitchen
shall be grounded with at least two separate twenty
ampere circuits. At least two duplex receptacles shall be readily accessible. Readily accessible
receptacles within six feet of sinks shall be GFCI protected.
d. In bathrooms, a duplex receptacle
with ground-fault circuit interrupter protection shall be
properly installed adjacent to the basin.
e. Basements shall have at least one
GFCI protected grounded duplex receptacle. This shall
be in addition to the laundry receptacle. All general purpose 120 volt receptacles in unfinished
areas shall be GFCI protected.
5. Wiring. Exposed knob and tube wiring and ungrounded
Romex shall be removed. All
concealed knob and tube wires extending into the basement shall be encased or protected in
nonmetallic flexible conduit (loom), metallic conduit, or other approved material. All such knob
and tube and ungrounded Romex extending into the basement shall terminate in a junction box
not more than twenty-four inches from the point of entrance.
6. Heating System. The heating system shall be placed
on a separate circuit.
7. Lighting. Every habitable room, kitchen, hallway, stairway
and attached garage shall have at
least one wall switch controlled lighting outlet. Switches shall be located near the door opposite
the hinges. Switch controlled receptacles may be permitted in habitable rooms, but shall be in
addition to the minimum duplex receptacles required. Switches shall be located so as to make
entrance into a dark area unnecessary. (Ord. 97/U-6146)