Chapter 20.08 ELECTRICAL CODE
Section 20.08.120 New construction or rewiring - all buildings.
The following are the minimum requirements for new construction or rewiring and are applicable to all
types of buildings.
1. Service Conductors.
a. Utility installed underground service laterals may
extend inside the customer's building and will be
exempt from National Electrical Code ampacity requirements provided there is no more than seven feet
of
conductor inside the building.
b. Service conductors shall be installed in electrical
metallic tubing or rigid metal conduit on the
exterior of the building and in rigid metal conduit on the interior of the building.
EXCEPTION: The service conductors may be installed in
rigid nonmetallic conduit for the riser to the
outdoor meter enclosure for underground services or where installed underneath the concrete basement
floor or encased in two inches of concrete or masonry.
2. Service Grounding.
a. All service grounding electrode conductors installed
shall be copper. When there is a metallic water
supply, the ground shall terminate on the street side of the water meter and be clamped on the customer
side
of the water meter.
b. The minimum sized grounding electrode conductor for
any service shall be No. 6 Copper.
c. All grounding shall comply with the National Electrical
Code as adopted by this code.
3. Panel Boards - Residential.
a. The distribution panel for an existing single-family
dwelling containing up to 2,000 square feet of
finished floor area, or area likely to be finished, shall be at least 100 ampere, three wire, single-main
disconnect type, with space for at least eighteen breakers.
b. The distribution panel for an existing single-family
dwelling containing over 2,000 square feet of
finished floor area, or area likely to be finished, shall be at least 150 ampere, three wire, single-main
disconnect type, with space for at least twenty-four breakers.
c. The distribution panel for a new single-family dwelling
containing up to 1,600 square feet of
finished floor area, or area likely to be finished, shall be at least 100 ampere three wire, single-main
disconnect type, with space for at least eighteen breakers.
d. The distribution panel for a new single-family dwelling
containing over 1,600 square feet of finished
floor area, or area likely to be finished, shall be at least 150 ampere, three wire, single-main disconnect
type, with space for at least twenty-four breakers.
Definition: Finished floor area shall be defined as the area which has a finished
floor or floor covering,
including hallways and closets.
4. All Residential Buildings.
a. The basement may be wired either in metal-clad cable
(BX) or fully grounded nonmetallic sheath
cable (Romex) where permitted. In unenclosed spaces where the wiring is run at right angles to
wood
joists, all wiring shall be run through holes bored in the approximate center of the joists, except
that the
wires may be stapled to the side of the joists, sill, plate or center beam.
b. The basement shall be lighted by a minimum of one
light for each three hundred square feet and one
light for each room.
c. All stairways are adequately illuminated. Stair
lights shall be controlled so it will not be necessary
to use stairs in the dark.
d. All electrical appliances which require a heavy-duty
or special outlet shall be connected to separate
and individual circuits with an approved flexible cord including an approved grounding cap having the
same configuration as the grounding receptacle. Appliance cords shall not exceed six feet in length.
If not wired direct, all garbage disposals, small sump pumps, humidifiers and
dehumidifiers, shall have
grounding-type cords with a matching grounding receptacle provided.
All garbage disposals shall be controlled by a wall switch and may be connected
to one of the kitchen
small appliance circuits.
e. All feeders shall be installed in an approved raceway
system.
f. All structures with more than twelve dwelling units
shall be wired in an approved raceway system.
g. Service entrance cable (SE), as defined in Article
338 of the National Electrical Code, shall not be
used for services or feeders. Service entrance cable (SE) shall be permitted for interior branch
circuits only
where the fully insulated conductors are used for circuit wiring and the uninsulated conductor is used
for
equipment grounding purposes.
h. Main, feeder and branch circuit breakers or fuses
shall be accessible to the tenant.
5. Commercial, Industrial, Institutional, and Places of Assembly.
a. All wiring for electric light and/or power hereafter
installed in churches, schools, theaters, motels,
hotels, lodges, nursing homes, and buildings classified as commercial or industrial and places used
for
public assembly of fifty persons or more, warehouses, and commercial, service, repair or storage garages
accommodating more than three cars, store buildings, factory buildings and their basements shall be
in an
approved raceway system.
b. Temporary Wiring. Circuit breakers shall be installed
for all fifteen and twenty ampere, one hundred
twenty volt receptacles installed for temporary purposes. Note: This is in addition to NEC, GFCI
requirements.
c. All new feeders run to distribution panels or new
or larger services installed are to have all wiring
and electrical apparatuses that are served by these panels or services updated to meet the minimum Sioux
City electrical code.
6. Closet lighting shall conform to specifications and clearances as set forth
in section 410-8 of the
National Electrical Code.
(Ord. 2000-9110; 97/U-6146)